SXD-QG01 Combustible Gas Detector
Specification · GB15322.2-2019 · Natural gas (Methane CH₄)
SXD-QG01 is a combustible gas detector designed for on-site detection of natural gas leaks: when the set concentration is reached, it triggers an audible and vi…
No. sxd-qg01-combustible-gas-detector · 2026-11-20
Overview
Product Positioning
SXD-QG01 is a combustible gas detector designed for on-site detection of natural gas leaks: when the preset concentration is reached, it triggers a sound-and-light alarm and pushes notifications to the platform, and can be linked to a shut-off valve and exhaust system—moving from "discovering it only after smelling gas" to "taking action as soon as the concentration is reached."
Core Functions
- Real-time natural gas concentration detection with tiered alarms
- On-site sound-and-light alarm + remote platform push notifications
- Supports linkage with emergency shut-off valves and exhaust equipment
Platform Integration
Alarms are sent to the platform via an IoT gateway, and on-duty personnel receive synchronous notifications on their mobile phones; the linkage logic can be configured on the platform side.
Deployment Essentials
Install above gas-using equipment or near pipeline connections (natural gas is lighter than air, so install high), and avoid locations directly exposed to cooking fumes; one unit is recommended per gas-using point.
FAQ
Q: How often should it be calibrated? A: Calibrate periodically according to the product instructions and local regulatory requirements; the platform records device self-checks and offline status.
Q: Can it automatically shut off the gas source? A: It supports linkage with a shut-off valve; an solenoid valve must be configured on site and installed by professional personnel.
Q: What should be done about false alarms? A: Alarm delay and concentration thresholds can be set to reduce false alarms caused by interference such as cooking fumes and alcohol concentration.
Related Recommendations
- Solution: Smart Campus Security Monitoring Upgrade Solution
- Solution: Smart Classroom Behavior Analysis Solution
References
The following are relevant regulations and standards for further verification:
- Food Safety Law of the People's Republic of China — Official Source
- Regulations on the Management of School Food Safety and Nutrition and Health (Order No. 45 of the Ministry of Education and two other departments) — Official Source
Applications




Core Features
GB15322.2-2019
天然气(甲烷 CHa)
半导体式
8% LEL
Specifications
| Item | Specification |
|---|---|
| Applicable Standard | GB15322.2-2019 |
| Gas Detected | Natural gas (Methane CH₄) |
| Detection Principle | Semiconductor type |
| Alarm Setpoint | 8% LEL |
| Alarm Method | Local audible and visual alarm |
Expand all(11)
| Alarm & Control Functions | Relay output: 1 normally open output (max. load 250 VAC/10A); Solenoid valve output: 1 channel 12V pulse output (pulse width 100 ms) |
|---|---|
| Local Data Storage | Records: 200 alarm events, 200 alarm recovery events, 100 fault events, 100 fault recovery events, 50 power-on events, 50 power-off events, 1 gas sensor failure event |
| Configuration Method | NFC (mobile app) |
| Power Supply | DC 12V/1A |
| Protection Rating | IP30 |
FAQ
How often should calibration be performed?
Calibrate regularly according to the product instructions and local regulatory requirements. The platform records device self-checks and offline status.
Can it automatically cut off the gas source?
It supports linkage with a shut-off valve; an solenoid valve must be configured on site and installed by professional personnel.
What should I do about false alarms?
You can set an alarm delay and concentration threshold to reduce false alarms caused by interference such as oil fumes and alcohol vapor.
Related Products
View All →
SXD-MC305 Rodent Barrier Door Sensor
SXD-MC305 is a wireless rat guard door sensor that monitors the open/closed status of the rat guard in real time: if the guard is not placed as required or is removed manually, the platform immediately receives an alert, preventing "rats from getting through and records from being traced."
Learn More →
SXD-GW1000 IoT Gateway
SXD-GW1000 is a LoRaWAN IoT gateway that unifies the connection and platform upload of sensor devices in commercial kitchens—including door magnetic contacts, temperature and humidity sensors, smoke detectors, and combustible gas detectors—solving the problem of "each sensor connecting separately and data scattered across multiple places."
Learn More →
SXD-WS303 Temperature and Humidity Sensor
SXD-WS303 is a temperature and humidity sensor designed for online temperature and humidity monitoring in commercial kitchens, warehouses, and cold storage rooms: it automatically triggers alarms when limits are exceeded and can be linked with exhaust and dehumidification equipment, turning "temperature out of limit" from a verbal reminder into a traceable record.
Learn More →
SXD-YG01 Smoke Detector
SXD-YG01 is a standalone photoelectric smoke detector designed for early smoke detection in unattended areas such as kitchens, warehouses, and electrical distribution rooms: it provides local audible and visual alarms and uploads data to the platform, while retaining independent alarm capability so it still sounds even when the network is down.
Learn More →Ready to go smart?
Leave a message or call us for tailored selection advice.